HSE Guidelines (Barrier Glands)

HSE Guidelines (Barrier Glands)

Health and Safety Executive (HSE) have released guidelines relating to the selection and installation of barrier glands.

These guidelines identify that Duty Holders should apply the Informative National Annex of BS EN 60079-14: 2014 as Relevant Good Practice when assessing the requirements for fitting a barrier gland to electrical equipment in potentially explosive atmospheres.

Please see below for the guidelines in full:

Use of Barrier Glands in Potentially Explosive Atmospheres to meet IEC 60079:14 2013 (Edition 5)

Health and Safety Executive – Safety Notice

Department Name:HID CEMHD (E,C&I team)
Bulletin No:HID 1-2016
Issue Date:1 February 2016
Target Audience:Chemical processing and production
Engineering
Warehousing
Offshore
Others: Duty holders designing, installing, inspecting and maintaining electrical equipment in potentially explosive atmospheres
COMAH Duty Holders and operators installing and maintaining electrical equipment in explosive atmospheres:
Key Issues:There is currently a key difference between the current IEC 60079-14: 2013 Standard and previous versions of BS EN 60079-14: 2008 & IEC 60079-14: 2007 for use of electrical equipment in potentially explosive atmospheres in that the IEC Standard currently allows the Duty Holder to use a ‘standard’ Ex certified flameproof gland as opposed to a Ex certified ‘barrier gland’ without the requirement to apply the previous flowchart used in the British Standard which identified glanding requirements based on gas group / zone / enclosure size. There is evidence that this approach creates a fire and explosion risk and this Notice provides Duty Holders with information on what action to take.

Introduction

There is currently a key difference between the current IEC 60079-14: 2013 Standard and previous versions of BS EN 60079 -14:2008 & IEC 60079- 14: 2007 for use of electrical equipment in potentially explosive atmospheres in that the IEC Standard currently allows the Duty Holder to use a ‘standard’ Ex certified flameproof gland as opposed to a Ex certified ‘barrier gland’ without the requirement to apply the previous flowchart used in the British Standard which identified glanding requirements based on gas group / zone / enclosure size. There is evidence that this approach creates a fire and explosion risk and this Notice provides Duty Holders with information on what action to take.

Background

The current International Standard, IEC 60079-14: 2013 Standard allows Duty Holders to use a ‘standard’ Ex certified flameproof gland as opposed to a Ex certified ‘barrier gland’ without the requirement to apply the previous flowchart used in the British Standard which identified the glanding requirements based on gas group / zone / enclosure size, provided that the Duty Holder uses:

IEC 60079-14: 2013, Clause 10.6.2

b) Cables and glands meeting all of the following:

  • Cable glands complying with IEC 60079-1
  • Cables used to comply with (Clause) 9.3.2 (a)
  • The connected cable is at least 3m in length.

There is credible independent evidence that this approach poses a risk of fire propagation through the cable sheath (after multiple ignitions) and therefore such a scenario may pose an ignition risk if the new IEC Standard is applied by Duty Holders, i.e. no barrier gland is used.

The 2014 version of BS EN 60079-14 does mirror the IEC Standard in respect of the above clause and requirements in the ‘Normative’ body of the Standard, however this version also contains a National Annex (NA) (see p138 onwards) that acknowledges the British Standards Institution’s (BSI) concerns over the application of the IEC Standard to the use of barrier glands (see below). Reference to this National Annex is also clearly stated in the ‘National foreword’ of the British Standard:

NA.4 UK committee concerns

1.The UK Committee is not aware of any issues (either unsafe or over-engineered situations) relating to the use of the selection chart since its adoption in the UK in 1989 and subsequent international adoption in 1996.

2.The UK Committee have not seen documented evidence of any tests carried out to justify either the removal of the selection chart or its replacement by the new selection procedure.

3.Verbal descriptions of recent tests seem to suggest that tests only relate to ignitions through the cable. The original ERA research project highlighted that severe thermal damage can be inflicted on the core insulation and bedding by the heat generated by multiple explosions within the enclosure. This could result in subsequent catastrophic failure of the cable leading to ignition of the surrounding atmosphere.

4.The selection chart only applied to flameproof enclosures which contained a source of ignition in normal operation, but the new procedure applies to all flameproof enclosures. Previously all junction boxes and indirect entry terminal boxes did not require barrier glands; however, under the new edition, unless the cable is at least 3m in length, a barrier gland will be required. The UK committee is unclear as to the justification for this change given that potential failures only arise after multiple ignitions.

Note 1 The new edition seeks to clarify the requirement for the cable to be at least 3m in length by referencing the new Annex E of the Standard. Annex E is titled “Restrictive breathing test for cables” and prescribes pressure drop tests with the cable connected to an enclosure. However, as this annex is informative, it is not clear whether cables will require testing to avoid the need for a barrier gland. The UK committee is of the opinion that such testing is not reasonably practicable.

AND

NA.5 Recommendation by the UK committee for users of this Standard and notice of future intent

  • Given the serious concerns expressed by the UK committee in relation to IEC 60079-14: 2013 (Edition 5), Clause 10.6.2 (b) throughout the whole revision process, they intend to submit a proposal to IEC to amend Edition 5.
  • Until such time as the situation is resolved, the UK committee recommend that users continue to consult the selection chart, reproduced as figure 1 in this Annex, to compliment the Standard.

 

At the moment this issue is being escalated by the BSI Technical Committee and the British Standard is also clear (although this National Annex section is ‘Informative’) that Duty Holders should continue to consult the existing flowchart (i.e. the selection chart – included in the NA annex Figure 1) to determine if a flameproof ‘barrier’ gland should be used.

Action required

HSE recognises the risks identified by the BSI Technical Committee and also has further independent 3rd party evidence that supports the BSI’s conclusions.

In order to ensure that this risk is suitably controlled, the HSE has defined the ‘Informative’ National Annex of BS EN 60079-14: 2014 as an ‘Established Standard’ (see http://www.hse.gov.uk/enforce/emm.pdf [1] ) as it is considered to be a “published or commonly known standard of performance interpreted by HSE as a level of performance needed to meet a general or qualified duty under health and safety“.

Duty Holders should therefore apply the Informative National Annex of BS EN 60079-14: 2014 as Relevant Good Practice when assessing the requirements for fitting a barrier gland to electrical equipment in potentially explosive atmospheres.

References

Control of Major Accident Hazards Regulations (COMAH) 2015
Dangerous Substances and Explosive Atmospheres Regulations 2002
BS EN 60079 -14: 2014 (National Annex)

Further information

Contact the HSE’s CEMHD Electrical, Control and Instrumentation team for further information on the subject or visit http://www.hse.gov.uk/eci/index.htm[2]

General note

This Safety Notice should be circulated to all relevant Duty Holders / Employees that are involved in the design, selection, installation, inspection and maintenance of electrical equipment in potentially explosive atmospheres.

Please contact us if you have any further questions

EXCELLENT
Google star 1Google star 2Google star 3Google star 4Google star 5
Based on 38 reviews
Posted on Google
michael casson
11 March 2026
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Great presentation by the instructors and prep for Compex 01 - 04 examination. Highly recommended
Posted on Google
Viaceslav Gaiducenia
12 January 2026
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
I did compex 01-04. English is not my first language. I got extra support, a bit of extra explonation, extra advice. All of this was super helpful. The instructors were very knowlagable, passionate and well tempered. I failed one of the units but I passed it second time.
Posted on Google
Cameron Bowyer
18 November 2025
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
I had an excellent experience training with EPIT Aberdeen. The instructors were incredibly knowledgeable, professional, and clearly passionate about what they do. The facilities and equipment are top-quality, and the training was delivered in a way that was both practical and engaging. Everything was explained thoroughly, with real-world examples that made the content easy to understand and apply. The staff were friendly and supportive throughout, creating a really positive learning environment. I left feeling confident, well-prepared, and genuinely impressed with the standard of training. Highly recommend EPIT Aberdeen to anyone looking for high-quality, industry-leading courses.
Posted on Google
Shawn Clark
12 September 2025
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Done the CompEx Ex01-Ex04 with Mike and Dodd, and they were both excellent! They both broke things down and made them easier to understand, as well as being genuinely good people who you can have a normal conversation and laugh with!
Posted on Google
John Soutar
11 June 2025
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
An absolutely brilliant training and test facility that made the dreaded "Compex Refresher" course, a far more enjoyable and beneficial experience. From the great training material to the very knowledgeable instructors, it all helped to teach us about the new practices and standards in Compex and I certainly left knowing more than I did when I walk through the door Monday morning. Thanks to the all staff! 5*
Posted on Google
Quinn MacDonald
30 April 2025
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Excellent facilities and the instructors were brilliant at teaching you the course materials along with real world advice and practices
Posted on Google
Andrei Lerca
4 March 2025
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Great training center powered by passionate people and a very beautiful reception.
Posted on Google
james Lombardo
27 November 2024
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Most reliable and Very professional
Posted on Google
Alistair Strachan (Ally)
17 September 2024
Google star 1Google star 2Google star 3Google star 4Google star 5Trustindex verifies that the original source of the review is Google.
Been here twice, superb facilities and certainly the best out of the 3 different venues I've attended for compex.

Booking Form - ECS Health and Safety Assessment

Please complete the form below and a member of our admin team will contact you regarding available dates.

Terms & Conditions
  • You are agreeing to pay all fees and expenses associated with the selected course.
  • Payment is required before commencement of the course.
  • The course fee includes refreshments, lunch and course material.
  • Failure to attend without prior cancellation will result in the loss of the fee.
  • Results will not be issued until payment has been received.
Cancellation Charges
  • 15 working days or less prior to the course start date, 100% cancellation charge will apply.
  • 16-20 working days prior to the course start date, 50% cancellation charge will apply.
  • 21-25 working days prior to the course start date, 25% cancellation charge will apply.

Read EPIT Group’s full Terms & Conditions and Privacy Policy.

CompEx Entry Requirements Guidance

Gases & Vapours (EX01 – Ex04)

Electrical / Instrument Craftpersons & Engineers Install, Inspect & Maintain: Gas & Vapours

Header Column #1
IndustriesPrincipal to all Ex environments, with direct application in hazardous vapour and gas environments.
Entry Qualifications
Guidance
Level 3, ECS Gold Card, National Diploma or equivalent. Disipline:
  • Electrotechnical
  • Instrumentation
Subject to knowledge, skill and experience candidates may benefit from Ex F+
Entry Knowledge - Expected
  • Knows the relevant legislative, regulatory, local requirements
  • Understands procedures for safe working practice and systems of work in an industrial setting
  • Can read and interpret relevant engineering drawings, related specifications, quality standards and equipment manuals
  • Understands the hierarchy of responsibilities in relation to reporting and decision-making
Entry Skills - Expected
  • Practical skills in engineering assembly of a complexity consistent with that of a level 3 craftsperson
  • Can apply safe working practices including safe isolation to meet the requirements of statutory and non-statutory regulations
  • Can safely install, inspect, test, commission, diagnose and correct faults in electrical plant, instrumentation, associated cabling, cabling supports and equipment
  • Can select, gland & terminate industrial type cables to a suitable component and associated cable tray in line with details on the appropriate specification
  • Can interpret manufacturers documentation for correct installation,maintenance and inspection
Job Roles
Aspiring to or operating in
  • Installation or Maintenance Electrician
  • Electrical or Instrument Technician
  • Engineers
Entry Experience
Guidance
  • 2 + years' experience operating in a site / industrial environment
  • Installing, inspecting, testing and/or maintaining equipment in an industrial setting
Entry Knowledge - Desirable
  • Understands the need for and methods of achieving safe working practice in gas and vapour Ex environments
  • Has basic practical, theoretical and technological knowledge and understanding of gas and vapour Ex environments
  • Has a basic understanding of the requirements, materials and equipment considerations, in relation to working in gas and vapour Ex environments
Entry Skills - Desirable
  • Can select and install a variety of Ex certified cables glands and terminate conductors into equipment
  • Can understand the principles of electrical protection concepts including selection, installation and maintenance
  • Understands intrinsically safe concept of protection and installation including the importance of documentation
  • Can inspect new and existing equipment in accordance with appropriate inspection techniques relevant to the different grades of inspection

CompEx Entry Requirements Guidance

Gases & Vapours (EX01 – Ex04)

Electrical / Instrument Craftpersons & Engineers Install, Inspect & Maintain: Gas & Vapours

Header Column #1
IndustriesPrincipal to all Ex environments, with direct application in hazardous vapour and gas environments.
Entry Qualifications
Guidance
Level 3, ECS Gold Card, National Diploma or equivalent. Disipline:
  • Electrotechnical
  • Instrumentation
Subject to knowledge, skill and experience candidates may benefit from Ex F+
Entry Knowledge - Expected
  • Knows the relevant legislative, regulatory, local requirements
  • Understands procedures for safe working practice and systems of work in an industrial setting
  • Can read and interpret relevant engineering drawings, related specifications, quality standards and equipment manuals
  • Understands the hierarchy of responsibilities in relation to reporting and decision-making
Entry Skills - Expected
  • Practical skills in engineering assembly of a complexity consistent with that of a level 3 craftsperson
  • Can apply safe working practices including safe isolation to meet the requirements of statutory and non-statutory regulations
  • Can safely install, inspect, test, commission, diagnose and correct faults in electrical plant, instrumentation, associated cabling, cabling supports and equipment
  • Can select, gland & terminate industrial type cables to a suitable component and associated cable tray in line with details on the appropriate specification
  • Can interpret manufacturers documentation for correct installation,maintenance and inspection
Job Roles
Aspiring to or operating in
  • Installation or Maintenance Electrician
  • Electrical or Instrument Technician
  • Engineers
Entry Experience
Guidance
  • 2 + years' experience operating in a site / industrial environment
  • Installing, inspecting, testing and/or maintaining equipment in an industrial setting
Entry Knowledge - Desirable
  • Understands the need for and methods of achieving safe working practice in gas and vapour Ex environments
  • Has basic practical, theoretical and technological knowledge and understanding of gas and vapour Ex environments
  • Has a basic understanding of the requirements, materials and equipment considerations, in relation to working in gas and vapour Ex environments
Entry Skills - Desirable
  • Can select and install a variety of Ex certified cables glands and terminate conductors into equipment
  • Can understand the principles of electrical protection concepts including selection, installation and maintenance
  • Understands intrinsically safe concept of protection and installation including the importance of documentation
  • Can inspect new and existing equipment in accordance with appropriate inspection techniques relevant to the different grades of inspection