A flameproof Ex db enclosure has a 32mm entry and we need to use it for a 20mm cable gland, is it permissible to use two reducers to achieve this?
Yes, BS EN IEC 60079-14, the standard for electrical installation of equipment states that to accommodate the entry devices and other fittings it is permitted to use either a single adapter; or one adapter with one reducer; or a maximum of two reducers. The standard also states that a blanking element (stopping plug) shall not […]
I have an Ex eb electric motor which is labelled as T3, I understand this to mean that the temperature reached by any part of the motor will not be any greater than 200°C. Is this the case and do I need to consider ambient temperature effects?
This is true, but the equipment must be installed in a location where the ambient temperature range does not exceed the ambient temperature range that the equipment has been designed for.
If an enclosure is marked II 2 GD and also Ex db IIC T5 Gb IP 66, Ex tb IIIC T100 Db, what is the meaning of the upper case and the lower case ‘d’s?
The upper case D is part of the ATEX labelling and indicates that the equipment is for use in areas where the explosion hazard is Dust (the G indicates Gas Hazard). The lower case d indicates the method of Ex protection, in this case flameproof.